Figure 1: Pressure safety valve at the discharge line of a gas compressor.
With competitive price and timely delivery, MetalsKingdom sincerely hope to be your supplier and partner.
Pressure relief valves and safety valves in the manufacturing industry can sometimes fail. Failure causes the valve to release pressure before the system reaches the maximum pressure or causes leakage and chattering. Troubleshooting the valve and the system for whats causing the issues is a safe practice. This article explores the causes of pressure relief valve failure in a system and how to test the valve to repair or replace it.
Pressure relief valves and safety valves are essential to keeping hydraulic and pneumatic systems below set pressure. Depending on the installation, they can either:
A properly maintained pressure relief valve can last up to thirty years. However, the pressure relief valve can fail over time. Its essential to recognize the signs to solve the problem quickly and keep the facility safe. There are multiple signs of pressure relief valve failures to watch out for while troubleshooting the system.
A system that cannot reach its designed pressure can be a sign of pressure relief valve failure that can cause a production slowdown. Checking the pressure relief valve can help determine the problem, and it is possible to fix the issue in some cases.
If the system pressure builds to above the maximum pressure, a pressure relief valve or safety valve should open up to let off the additional pressure, keeping the facility and equipment safe. However, if the pressure relief valve does not open when the system pressure rises above the maximum set pressure, there is likely an issue with the valve. Ensure that the valve is calibrated to the correct set pressure, and also examine the facility thoroughly to determine what caused the excess pressure. Contaminants like dirt, dust, and corrosion can cause the valve to remain stuck. Replace the pressure relief valve if the excessive buildup cannot be cleaned. Read our article on pressure relief valve installation for more information on how to replace and install a new pressure relief valve.
A valve can leak for multiple reasons:
To fix a leaking pressure relief valve:
There are three types of testing methods to test a pressure relief valve.
With bench testing, the user has to completely shut down the facilitys system and remove all pressure relief valves. These valves go to a laboratory to be tested and repaired as necessary. After repair, the valves reinstall into the system. Bench testing is the most thorough testing method; pressure relief valves undergo this testing method when manufactured.
The inline testing procedure doesnt require the removal of valves or facility downtime. A trained technician can test the valves in the system to calculate their setpoints. Inline testing is popular for regular mandatory inspections and provides accurate results by eliminating the need for downtime. The method offers real-time, in-system reporting and also eliminates transportation-related damage.
Manual testing on site is possible for certain pressure relief valves. To perform an operated-in-place test, manually activate the test lever on the pressure relief valve. This test ensures that the valve can open and shut tightly, but it fails to verify at what pressure the valve opens and shuts. This is a basic test done quarterly or bi-annually on pressure relief valves and ensures the most basic functionality of pressure relief valves.
Figure 2: Testing a pressure relief valve: pressure regulator (A), needle valve (B), test gauge (C), pressure relief valve (D), test jig (E), and release point (F).
Figure 2 shows the functional testing procedure of a pressure relief valve. Before starting the experiment, check the pressure relief valves datasheets and ensure the experiment complies with the manufacturers guidelines. Also, check if the valve is correctly calibrated to its set point.
Once the pressure relief valve functions well after repairing or replacing the damaged valve, implement a routine of regular maintenance and testing. A damaged pressure relief valve can pose severe hazards to the functionality of a facility.
Note: Do not remove the manufacturers seal or adjust the setting during the tests.
Table 1: ASME code stating the tolerance values with respect to the set pressure
ASME code section I
For more information, please visit Safety Relief Valve Repair Machining.
Set pressure Tolerance 1.0 - 5.0 Kg/Cm2 G ± 0.14 Kg/Cm2 G 5.1 - 21.0 Kg/Cm2 G ± 3% 21.1 - 70.0 Kg/Cm2 G ± 0.70 Kg/Cm2 G > 70.0 Kg/Cm2 G ± 1%Table 2: Leakage rate for valve testing as per API 527
Set pressure at 15.6 degrees celsius (60 degrees Fahrenheit)MPA (psig)
Orifice diameter < 18mm (0.7 in)Leakage rate (bubbles/min)
Orifice diameter > 18mm (0.7 in)Leakage rate (bubbles/min)
0.013 6.896 (15-) 40 20 10.3 () 60 30 13.8 () 80 40 17.2 () 100 50 20.7 () 100 60 27.6 () 100 80 34.4 () 100 100 41.4 () 100 100API 576 states to test the pressure relief valve as often as needed to maintain the device in a satisfactory operating condition. This means inspecting and testing the valve in accordance with an established schedule for continuously operating valves. The required testing frequency depends on the application. For example, test a pressure relief valve installed in a corrosive and polluted environment more frequently than one installed in a non-corrosive environment. Some conditions that call for shorter testing time intervals include:
Also, look at the valves testing history over time. Test the valve less often if it consistently passes the test. For new processes where the testing conditions cannot be accurately predicted, perform the initial inspection as soon as possible after the operations begin to establish a suitable and safe testing interval. Test the pressure relief valve after every fire event. Service and replace the valves seal gasket if the valve pops open.
Yes, leaking pressure relief valves can cause overpressure conditions leading to system failure and explosions. Diagnose the problem and repair or replace the valve as needed.
Shut down the system, tighten or replace the bonnet bolts, and tighten the packing gland nuts. If the valve still doesnt work properly, replace the valve.
Vapor and other compressible fluid passing through the pressure-reducing portion of the valve can cause the fluids mechanical energy to convert into sound energy causing squealing.
A pressure valve is used for the protection of pressure vessels such as piping systems and other pressure applications, in case the pressure exerted on them exceeds the pressure allowed by their design. However, a pressure relief valve does not control or regulate the pressure in the pressure application. It functions only in the case of overpressure.
Since water heaters can at any given time have steam, cooling water, etc. inside them, they are pressure applications which can be relieved with a pressure valve. However, in the case that the valve itself caves in and breaks, there can be drastic outcomes if not dealt with in time. They can result in flooding, your bills will go up since a faulty water heater will use more energy, and in the worst-case scenario it might even explode. A broken relief valve is no relief at all and should be repaired or replaced as soon as possible in order to avoid mishaps and injuries.
Theres no better way to know if a valve is broken than to check it. Twice every year, you should test your water heater to see if it is leaking. Testing a pressure valve for leaks is pretty easy and takes less than 5 minutes. Be sure to wear gloves and goggles for safety and be very careful since the water in that tank is going to be piping hot. If youre not careful, you could end up burning or scalding yourself. To test, take a small vessel and place it under the outlet (the outlet is the part which faces down). Very slightly and very carefully, begin to open the pressure valve. Dont open it completely since the water inside is hot, and go no more than 60 degrees from the position the valve was originally in. Upon opening, the water should fall down in a rapid movement, accompanied by a hissing noise due to the pressure. This indicates that the valve is running perfectly fine. If there is no water coming out, then the valve most likely leaks. Contact a repairman or immediately get it replaced. Similarly, when you release the valve the water should stop pouring. In case the water is still dripping, the valve is probably broken. Under no circumstances should you ignore the leak.
Shut down the dialers on the heater which stand for cold water and gas. In the outlet at the bottom, connect a hose. Using a big bucket (around 5 gallons will do), empty the heater of the water using the hose. Be careful since the water is still pretty hot. Once the water has been removed, you can take away the discharge tube. This you do by opening it gently and partially (not completely), and check if theres still water coming out. Place a vessel underneath the valve just in case. If theres still water there, drain more from the heater. Once the water stops pouring, unscrew the relief valve using a pipe wrench. Look up the pressure settings for your valve and buy a new one with the same settings. If unsure about your involvement in the repair, you can always reach out to Miami Water Heater and our professionals will take care of the job for you.
Are you interested in learning more about Bi Pipe Machine? Contact us today to secure an expert consultation!